Remote Sensor Wiring Diagrams

5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802 Page 1 of 1 REMOTE SENSOR R C 24 VOLTS REMOTE SENSOR WIRING DIAGRAMS SINGLE REMOTE …The Remote Sensor must be wired to the RS thermostat sensor pigtails with field supplied 2- conductor shielded wire.• The Remote Sensor wiring must not exceed 200′.• The 2-sensor conductors are connected to the thermostat pigtails with wire nuts, and screw terminals on the sensor mounting base.• The shield conductor is cut and taped at the …
REMOTE SENSOR WIRING DIAGRAMS SINGLE REMOTE SENSOR • The Remote Sensor must be wired to the RS thermostat sensor pigtails with field supplied 2- conductor shielded wire. • The Remote Sensor wiring must not exceed 200′. • The 2-sensor conductors are connected to the thermostat pigtails with wire nuts, and screw terminals on the sensor mounting base. • The shield conductor is cut and taped at the sensor and connected to the C terminal on the thermostat. SHIELD Sensor Wire 2 cond 18 - 22 AWG solid wire with shield • The Remote Sensor is designed to be installed with Zonex Systems thermostats only: DIGICOMRS DIGIHPRS ModStatRS and MODS2RS. NOTE: The thermostat must indicate RS on the end of the model designation to be compatible. • To remove the sensor cover, use a 1/16″ Allen wrench on bottom set screws. REMOTE MULTIPLE SENSOR AVERAGING…